BAIHP supported IBACOS by testing (Table below) and rating the home. Data collected at this home by IBACOS will be processed and archived with support from FSEC’s data management system.
Test
Results for 2005 New American Home |
||
| Test | Measurements | Notes |
| Whole House Air Tightness | CFM50=5552 ACH50=5.0 |
C=549, n=0.591, r=.9996 |
| Duct Leakage AHU1 Master Suite | CFM25,total = 160 CFM25,out = 48 |
3 Ton AHU Flow = 1203 |
| Duct Leakage AHU2 | CFM25,total = 300 CFM25,out = zero |
5 Ton AHU Flow = 1550 |
| Duct Leakage AHU3 Suite 2 | CFM25,total = 104 CFM25,out = 32 |
2 Ton AHU Flow = 898 |
| Duct Leakage AHU4 Foyer | CFM25,total = 155 CFM25,out = 40 |
2 Ton AHU Flow = 1120 |
| All Duct Leakage | CFM25,total = 719 CFM25,out = 120 |
12 Tons AHU Flow = 4771 |